Справочник Пользователя для Mitsubishi Electronics FR-A500

Скачать
Страница из 257
148
4.2.43 Commercial power supply-inverter switch-over function
 
(Pr. 135 to Pr. 139)
Pr. 135 "commercial power supply-inverter
switch-over sequence output terminal selection"
Pr. 136 "MC switch-over interlock time"
Pr. 137 "start waiting time"
Pr. 138 "commercial power supply-inverter 
switch-over selection at alarm occurrence"
Pr. 139 "automatic inverter-commercial power
supply switch-over frequency"
The inverter contains a complicated sequence circuit for commercial power supply-inverter operation switch-
over. Hence, the magnetic contactors for switch-over can be interlocked easily by merely entering the start,
stop or automatic switch-over select signal.
(1)  Wiring example
Sink logic, Pr. 185 = 7, Pr. 186 = 6, Pr. 192 = 17, Pr. 193 = 18, Pr. 194 = 19
Parameter 
Number
Factory
Setting
Setting Range
Remarks
135
0
0, 1
136
0.1 s
0 to 100.0 s
137
0.5 s
0 to 100.0 s
138
0
0,1
139
9999
0 to 60.0Hz, 9999
9999: No automatic 
switch-over
Related parameters
Pr. 11 "DC injection brake operation
time"
Pr. 57 "restart coasting time"
Pr. 58 "restart cushion time"
Pr. 180 to Pr. 186
(input terminal function selection)
Pr. 190 to Pr. 195
(output terminal function selection)
MC1
STF
CS
MRS
RES
SD
10
2
5
U
V
W
MC2
×
MC3
IM
IPF
OL
SE
*1
*1
*1
*2
MC3
MC2
24VDC
MC
1
FU
NFB
MC
2
MC
3
*3
OH
SU
IPF
OL
FU
SE
24VDC
External thermal relay
Reset
Frequency setting signal
External
thermal relay
Signal set in Pr. 190 to Pr. 195
*3. The terminals used depend on the Pr. 180 to Pr. 186 settings.
*1. Note the sequence output terminal capacities. The terminals used 
     depend on the Pr. 190 to Pr. 195 settings.
Output Terminal Capacity
Permissible Output Terminal Load
Inverter's open collector outputs
(IPF, OL, FU)
24VDC 0.1A
FR-A5AR (option output)
230VAC 0.3A
30VDC 0.3A
*2. When connecting an AC power supply, connect the FR-A5AR option 
     and use the contact output.
     When connecting a DC power supply, install the following protective 
     diode.
Inverter
Operation interlock
Inverter start 
(forward rotation)
Inverter-commercial 
power supply 
switch-over
RA
R
S
T
R1
S1
Note:  
‚
This switch-over function is used in the external operation 
            mode. Always connect terminals R1, S1 to a different
            power supply (power supply different from the one for MC1) 
            to ensure proper operation.
           
‚
MC2 and MC3 must be mechanically interlocked.