4.2.52 Output terminal function selection (Pr. 190 to Pr. 195)
Pr. 190 "RUN terminal function selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "A, B, C terminal function selection"
You can change the functions of the open collector and contact output terminals.
<Setting>
Refer to the following table and set the parameters:
Parameter 
Number
Terminal 
Symbol
Factory Setting
Factory-Set
Terminal Function
Setting Range
190
RUN
0
Inverter running
0 to 199, 9999
191
SU
1
Up to frequency
0 to 199, 9999
192
IPF
2
Instantaneous power 
failure/undervoltage
0 to 199, 9999
193
OL
3
Overload alarm
0 to 199, 9999
194
FU
4
Output frequency 
detection
0 to 199, 9999
195
A, B, C
99
Alarm output
0 to 199, 9999
Setting
Signal 
Name
Function
Operation
Related 
parameter
Positive 
logic
Negative 
logic
0
100
RUN
Inverter running
Output during operation when the inverter output 
frequency rises to or above the starting 
frequency.

1
101
SU
Up to frequency
Refer to Pr. 41 "up-to-frequency sensitivity". 
(Note 2)
Pr. 41
2
102
IPF
Instantaneous power failure or 
undervoltage
Output when an instantaneous power failure or 
undervoltage occurs.

3
103
OL
Overload alarm
Output while stall prevention function is activated.
Pr. 22, Pr. 23, 
Pr. 66, Pr. 148, 
Pr. 149, Pr. 154
4
104
FU
Output frequency detection
Refer to Pr. 42, Pr. 43 (output frequency 
detection).
Pr. 42, Pr. 43
5
105
FU2
Second output frequency 
detection
Refer to Pr. 50 (second output frequency 
detection).
Pr. 50
6
106
FU3
Third output frequency 
detection
Refer to Pr. 116 (third output frequency 
detection).
Pr. 116
7
107
RBP
Regenerative brake pre-alarm
Output when 85% of the regenerative brake duty 
set in Pr. 70 is reached.
Pr. 70
8
108
THP
Electronic overcurrent 
protection pre-alarm
Output when the cumulative electronic 
overcurrent protection value reaches 85% of the 
preset level.
Pr. 9
9
109
PRG
Programmed mode
Output in the programmed mode. (Note 3)
Pr. 79, Pr. 200 
to Pr. 231
10
110
PU
PU operation mode
Output when the PU operation mode is selected.

11
111
RY
Inverter operation ready
Output when the inverter can be started by 
switching the start signal on or while it is running.

12
112
Y12
Output current detection
Refer to Pr. 150 and Pr. 151 (output current 
detection).
Pr. 150, Pr. 151
13
113
Y13
Zero current detection
Refer to Pr. 152 and Pr. 153 (zero current 
detection).
Pr. 152, Pr. 153
14
114
FDN
PID lower limit
Refer to Pr. 128 to Pr. 134 (PID control).
Pr. 128 to 
Pr. 134
15
115
FUP
PID upper limit
16
116
RL
PID forward-reverse rotation 
output