4.2.61 High-speed frequency control (Pr. 271 to Pr. 274)
Pr. 271 "high-speed setting maximum current"
Pr. 272 "mid-speed setting minimum current"
Pr. 273 "current averaging range"
Pr. 274 "current averaging filter constant"
z
Used to set the current, averaging range, etc. required when "2" or "3" is set in Pr. 270 to select load torque
high-speed frequency control.
<Wiring example>
• Sink logic
• Pr. 186 = 19
Parameter 
Number
Factory
Setting
Setting Range
271
50%
0 to 200%
272
100%
0 to 200%
273
9999
0 to 400Hz, 9999
274
16
1 to 4000
(Note) When load torque high speed 
frequency control is selected, 
automatic restart after instantaneous 
power failure function is invalid.
Note:  The input signal terminal used depends on the Pr. 180 to Pr. 186 settings.
R elated param eters
Pr. 4 "multi-seed setting (high speed)"
Pr. 5 "multi-seed setting (middle speed)"
Pr. 6 "multi-seed setting (low speed)"
Pr. 59 "remote setting function selection"
Pr. 180 to Pr. 186
  (input terminal function selection)
Pr. 270 "stop-on-contact/load torque 
high-speed control selection"
The lift with a light load or without
 a load is moved faster than the
lift with a load.
(The output frequency is increased.) 
<With high-speed frequency control>
<Without high-speed frequency control>
Whether there is a load or
not, the lift is moved vertically
at the same speed.