5.1  Errors (Alarms)
If any fault has occurred in the inverter, the corresponding protective function is activated and the error 
(alarm) indication appears automatically on the PU display. When the protective function is activated, refer to 
"5.2 Troubleshooting" and clear up the cause by taking proper action. If an alarm stop has occurred, the 
inverter must be reset to restart it.
When the protective function is activated, take the corresponding corrective action, then reset the inverter, 
and resume operation.
Resetting method
When the protective function is activated and the inverter has stopped its output, the inverter output is kept 
stopped (and the motor is coasted to a stop). Unless reset, therefore, the inverter cannot restart. To reset,  
use any of the following methods: switch power off once, then on again; short reset terminal RES-SD for 
more than 0.1s, then open; or press the 
 key of the operation panel or parameter unit (use the 
help function of the parameter unit). If RES-SD are kept shorted, the operation panel shows "Err."  and the 
parameter unit indicates that the inverter is being reset.
5.1.1
Error (alarm) definitions
(1)  Major faults
When the protective function is activated, the inverter output is shut off and the alarm is output.
Operation Panel  
Indication
E.OC1
FR-PU04
OC During Accs
Name
Overcurrent shut-off during acceleration
Description
When the inverter output current reaches or exceeds approximately 200% of the 
rated current during acceleration, the protective circuit is activated to stop the 
inverter output.
This indication also appears when the start signal is entered with power supplied to 
the R1 and S1 terminals only. 
Check point
Check for sudden acceleration.
Check for long descending acceleration time of lift applications.
Check for output short circuit.
Check that main circuit power (R, S, T) is supplied.
Corrective action
• Increase the acceleration time. (Decrease the descending acceleration time.)
• If "E.OC1" is always lit at a start, disconnect the motor once and then start the 
inverter. If "E.OC1" is still lit, contact your sales representative.
• Supply main circuit power (R, S, T).
Operation Panel  
Indication
E.OC2
FR-PU04
Stedy Spd OC
Name
Overcurrent shut-off during constant speed
Description
When the inverter output current reaches or exceeds approximately 200% of the 
rated current during constant speed, the protective circuit is activated to stop the 
inverter output.
Check point
Check for sudden load change.
Check for output short circuit.
Corrective action
Keep load stable.