Insulation resistance test using megger
1) Before performing the insulation resistance test using a megger on the external circuit, disconnect the
cables from all terminals of the inverter so that the test voltage is not applied to the inverter.
2) For the continuity test of the control circuit, use a meter (high resistance range) and do not use the megger
or buzzer.
3) For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not
perform the test on the control circuit. (Use a 500VDC megger.)
6.1.5
Pressure test
Do not conduct a pressure test. The inverter's main circuit uses semiconductors, which may be deteriorated
if a pressure test is made.
6.1.6
Daily and periodic inspection
Area of 
Inspec-
tion
Inspec
tion 
Item
Description
Interval
Method
Criterion
Instrument
Cus-
tomers
check
Daily
Periodic
1
year
2
year
General
Sur-
round-
ing 
environ-
ment
Check ambient 
temperature, humidity, 
dust, dirt, etc.
{
(Refer to page 10)
Ambient 
temperature:
(constant torque) 
-10
°
C to +50
°
C, 
non-freezing.
(Variable torque) 
-10
°
C to +40
°
C, 
non-freezing 
Ambient humidity: 
90% or less, 
non-condensing.
Thermometer, 
hygrometer, 
recorder
Overall 
unit
Check for unusual 
vibration and noise.
{
Visual and 
auditory checks.
No fault.
Power 
supply 
voltage
Check that the main 
circuit voltages are 
normal.
{
Measure voltages 
across the inverter 
terminal block R-
S-T phases.
Within 
permissible AC 
voltage fluctuation
(Refer to page 
220.)
Tester, digital 
multimeter
Main 
circuit
Gen-
eral
(1) Check with megger 
(across main circuit 
terminals and earth 
(ground) terminal).
(2) Check for loose 
screws and bolts.
(3) Check for overheat 
traces on the parts.
(4) Clean.
{
{
{
{
(1) Disconnect all 
cables from the 
inverter and 
measure 
across 
terminals R, S, 
T, V, W  and 
earth (ground) 
terminal with 
megger.
(2) Re-tighten.
(3) Visual check.
(1) 5M 
Ω
 or 
more.
(2), (3) No fault.
500VDC 
class megger
Conduc-
tors, 
cables
(1) Check conductors 
for distortion.
(2) Check cable 
sheaths for 
breakage.
{
{
(1), (2) Visual 
check.
(1), (2) No fault.
Termi-
nal 
block
Check for damage.
{
Visual check.
No fault
U
V
W
IM
Inverter
Motor
Power
supply
500VDC
megger
Earth (ground) terminal
R
S
T