Wiring of the control circuit
(1)  Wiring instructions
1) Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. Do not earth
(ground) these terminals. Avoid connecting the terminals SD and 5 and the terminals SE and 5.
2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the
main and power circuits (including the 200V relay sequence circuit).
3) Since the control circuit input signals are micro currents, use two or more parallel micro signal contacts or
a twin contact to prevent a contact fault.
4) It is recommended to use the cables of 0.75mm
2
 gauge for connection to the control circuit terminals.
If the cable gauge used is 1.25mm
2
 or more, the front cover may be lifted when there are many cables
running or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.
(2)  Terminal block layout
 
In the control circuit of the inverter, the terminals are arranged as shown below:
Terminal screw size: M3.5
Tightening torque: 1.2N
m