76
4.2.4
Multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
Pr. 4 "multi-speed setting (high speed)"
Pr. 5 "multi -speed setting (middle speed)"
Pr. 6 "multi -speed setting (low speed)"
Pr. 24 to Pr. 27 "multi-speed setting
                   (speeds 4 to 7)"
Pr. 232 to Pr. 239 "multi-speed setting
                   (speeds 8 to 15)"
Used to preset the running speeds in parameters and switch between them using terminals.
z
Any speed can be selected by switching on-off the contact signal (RH, RM, RL or REX signal).
z
By using these functions with Pr. 15 "jog frequency", Pr. 1 "maximum frequency" and Pr. 2 "minimum
frequency", up to 18 speeds can be set.
z
Valid in the external operation mode or PU/external combined operation mode (Pr. 79 = "3 or 4").
<Setting>
• Set the running frequencies in the corresponding parameters.
Each speed (frequency) can be set as desired between 0 and 400Hz during inverter operation.
After the required multi-speed setting parameter has been read, the setting can be changed by pressing
the 
 key. (In this case, when you release the 
 key, press the 
 key to store the set
frequency. When using the FR-PU04 (option), press the  key.)
• Use any of Pr. 180 to Pr. 186 to assign the terminal used to input the REX signal.
Parameter 
Number
Factory Setting
Setting Range
Remarks
4
60Hz
0 to 400Hz
5
30Hz
0 to 400Hz
6
10Hz
0 to 400Hz
24 to 27
9999
0 to 400Hz, 9999
9999: Not selected
232 to 239
9999
0 to 400Hz, 9999
9999: Not selected
Note: 1. The priorities of the frequency commands are in order of jog, multi-speed operation, No. 4 terminal and
No. 2 terminal.
2. The multi-speeds can also be set in the PU or external operation mode.
3. For 3-speed setting, if two or three speeds are simultaneously selected, priority is given to the frequency
setting of the lower signal.
4. Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
5. The parameter values can be changed during operation.
6. When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be affected.
Check the functions of the corresponding terminals before making setting.
7. When only the REX signal on and Pr. 232 = "9999",  the set frequency is changed to the value  of low
speed operation command (Pr. 6). 
Related parameters
Pr. 1 "maximum frequency"
Pr. 2 "minimum frequency"
Pr. 15 "jog frequency"
Pr. 28 "multi-speed input compensation"
Pr. 29 "acceleration/deceleration
pattern"
Pr. 79 "operation mode selection"
Pr. 180 to Pr. 186 (input terminal
function selection)
ON
ON
ON ON ON
ON
ON
ON
ON
ON
ON
RH
RM
RL
Speed 7
Outpu
t fr
eque
ncy (
H
z
)
Speed 1
(high speed)
Speed 2
(middle speed)
Speed 3
(low speed)
Speed 4
Time
Speed 5
Speed 6
ON
ON
ON ON ON ON ON ON
ON
ON
ON
ON
ON ON
ON ON
ON ON ON ON
RH
RM
RL
REX
Speed 15
O
u
tp
u
t f
req
ue
nc
y (H
z
)
Time
Speed 9
Speed 8
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
When Pr. 232 = "9999" , frequency as set in Pr. 6 is output  (Note 7)
SET