4.2.10 Jog operation (Pr. 15, Pr. 16)
Pr. 15 "jog frequency"
Pr. 16 "jog acceleration/deceleration time"
In the external operation mode, jog operation can be started and stopped by the start signal (STF, STR) with
the jog signal ON, after selection of the jog operation function using the input terminal function selection. In
the PU operation mode, jog operation can also be performed using the PU (FR-DU04/FR-PU04).
z
 Set the frequency and acceleration/deceleration time for jog operation
Parameter Number
Factory Setting
Setting Range
Remarks
15
5Hz
0 to 400Hz
16
0.5 s
0 to 3600 s
When Pr. 21 = 0
0 to 360 s
When Pr. 21 = 1
Note: 1. In S-shaped acceleration/deceleration pattern A, the set time is a period of time required to reach
Pr. 3 "base frequency".
2. The acceleration time and deceleration time cannot be set separately for jog operation.
3. The value set in Pr.15 "jog frequency" should be equal to or greater than the Pr.13 "starting
frequency" setting.
Related parameters
Pr. 20 "acceleration/deceleration 
reference frequency"
Pr. 21 "acceleration/deceleration time 
increments"
Pr. 79 "operation mode selection"
Pr. 180 to Pr. 186
(input terminal function selection)
Pr.20
Pr.15
Pr.16
ON
ON
ON
Reverse rotation STR
Output frequency (Hz)
Jog frequency
setting range
Reverse
rotation
Time
Forward
rotation
Forward rotation STF
JOG signal