"UniVert 2" inverter 
 
Page 17 of 42 
8000012364 BAL, en 
Function of the Inverter 
For technical data or unit settings, refer to the Technical Data Sheet 
in chapter 8. 
3.1 DC 
Input 
The inverter is operated with 48 V (or 60 V) DC voltage. The input 
voltage is fuse-protected outside the INV. For details, refer to the 
technical data. 
An integrated softstart device limits the making current of the inverter 
to a value smaller than the rated input current. The input voltage is 
continuously monitored. (See chapter 3.3.) 
3.2 AC 
Output 
The INV output voltage is regulated to 230 V 50 H (see chapter 3.9) 
and monitored (see chapter 3.5). With an output voltage present and 
the INV in operation, the green LED lights up "U
OK". 
3.3 
DC Input Monitoring System 
If a value falls below the "DC undervoltage, switch-off" threshold, the 
INV is immediately switched off. If the input voltage rises above the 
acknowledgement value, the INV is switched back on. If the 
monitoring system is triggered, the red "U
I
<" LED lights up. 
 
It the "DC overvoltage, switch-off" threshold is exceeded, the red 
"U
I
>" LED lights up and the INV is immediately switched off. If the 
value falls below the "DC overvoltage, switch-off" acknowledgement 
value, acknowledgement is made after a delay of 15 seconds. 
3.4 
Temperature Monitoring System 
Overtemperature is signalled by the red "
ϑ>" LED if the heat sink 
temperature exceeds critical values. The faulty unit switches off after 
40 seconds. Acknowledgement is made when it has cooled down. 
Overtemperature can result from e.g. high ambient temperature, 
constant overload of the INV or from fan failure. 
3.5 
Output Voltage Monitoring System 
The INV output voltage is regulated to 230 V 50 Hz (see chapter 3.9) 
and monitored. With an output voltage present and the INV in 
operation, the green "U
OK" LED lights up. When the output voltage 
drops below 90% of the rated value, e.g. due to overload, short circuit 
or the triggering of a miniature circuit-breaker, the INV switches off 
after 2.5 seconds. The unit is not automatically switched back on. 
3.6 
Monitoring of Functions 
After connecting the input voltage, the self-test of the microcontroller 
control system is carried out automatically.