Справочник Пользователя для Mitsubishi Electronics FR-D720S-0.1K to 2.2K

Скачать
Страница из 52
30
Simple mode parameters
7
7 PARAMETERS
Simple variable-speed operation can be performed with the inverter in the initial settings. Set the required parameters
according to the load and operating conditions. Use the operation panel to set or change a parameter. (Refer to 
Chapter 4
of the Instruction Manual (Applied) for the detailed description of parameters. 
7.1 Simple mode parameters
POINT
In the initial setting, only the simple mode parameters are displayed by the Pr.160 Extended function display selection
setting. Change the Pr.160 Extended function display selection setting as required. (Refer to page 57 to change the
parameter.
Parameter 
Number
Name
Unit
Initial 
Value
Range
Application
0
Torque boost
0.1%
6%/4%/3%/
2%
*
0 to 30%
Use this parameter to increase starting torque under V/F 
control. Use this when a loaded motor cannot be driven 
and the warning [OL] occurs, then the inverter trips with 
[OC1] under V/F control.
∗ Initial value depends on the inverter capacity. 
(0.75K or lower/1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
1
Maximum frequency
0.01Hz
120Hz
0 to 120Hz
Use this parameter to set the upper limit for the output 
frequency.
2
Minimum frequency
0.01Hz
0Hz
0 to 120Hz
Use this parameter to set the lower limit for the output 
frequency.
3
Base frequency
0.01Hz
60Hz
0 to 400Hz
Use this parameter when the rated motor frequency is 50Hz.
Check the rating plate of the motor.
4
Multi-speed setting (high speed) 0.01Hz
60Hz
0 to 400Hz
Use these parameters to change among pre-set operation 
speeds with the terminals. The speeds are pre-set with 
parameters. 
5
Multi-speed setting (middle 
speed)
0.01Hz
30Hz
0 to 400Hz
6
Multi-speed setting (low speed) 0.01Hz
10Hz
0 to 400Hz
7
Acceleration time
0.1s
5s/10s/15s
*
0 to 3600s Use these parameters to set the acceleration/deceleration 
time.
∗ Initial value depends on the inverter capacity.
(3.7K or lower/5.5K, 7.5K/11K, 15K)
8
Deceleration time
0.1s
5s/10s/15s
*
0 to 3600s
9
Electronic thermal O/L relay
0.01A
Rated
inverter 
current
0 to 500A
With this parameter, the inverter protects the motor from 
heat. 
Set the rated motor current.
79
Operation mode selection
1
0
0
External/PU switchover mode
1
Fixed to PU operation mode
2
Fixed to External operation mode
3
External/PU combined operation mode 1
(Start command from External, frequency command from 
PU)
4
External/PU combined operation mode 2
(Frequency command from External, start command from 
PU)
6
Switchover  mode
7
External operation mode (PU operation interlock) 
125
Terminal 2 frequency setting 
gain frequency
0.01Hz
60Hz
0 to 400Hz
Use this parameter to change the frequency at the 
maximum potentiometer setting (5V in the initial setting)
126
Terminal 4 frequency setting 
gain frequency
0.01Hz
60Hz
0 to 400Hz
Use this parameter to change the frequency at the 
maximum current input (20mA in the initial setting)
160
Extended function display 
selection
1
9999
0
Simple mode + extended mode parameters are displayed.
9999
Only the simple mode parameters are displayed.
Pr.CL
Parameter clear
1
0
0, 1
Setting "1" returns all parameters except calibration 
parameters to the initial values.
ALLC
All parameter clear
1
0
0, 1
Setting "1" returns all parameters to the initial values.
Er.CL
Fault history clear
1
0
0, 1
Setting "1" clears eight past faults.
Pr.CH
Initial value change list
Displays and sets the parameters changed from the initial 
value.