Before You Begin 
Page 1-2
Confirming the Location of the Control Unit 
1
Confirming the Location of 
the Control Unit
1
Before installation, a room, closet, or other area must be designated where the 
system control unit can be mounted on the wall. The area must meet the 
environmental requirements in 
Table 1–1
.
Table 1–1. 
Environmental Requirements
!
CAUTION:
The AC outlet for the control unit should not be switch-controlled. 
Plugging the control unit into an outlet that can be turned on and off 
by a switch can cause accidental disconnection of the system.
The AC outlet must be properly grounded by using an AC receptacle 
for a 3-prong plug.
Do not install the control unit outdoors.
Do not place the control unit near extreme heat (furnaces, heaters, 
attics, or direct sunlight).
Do not expose the control unit to devices that generate electrical 
interference (such as arc welders or motors).
Conditions
Requirements
Distances
Within 25 cable feet (7.6 m) of the network interface 
(cannot be installed outdoors)
Within 1000 cable feet (304.8 m) of telephones 
Within 5 cable feet (1.5 m) of a dedicated AC power outlet 
(one outlet for every carrier)
Heat 
Dissipation
Fully loaded basic carrier: 500 Btu/hr (35 cal/sec)
Fully loaded 2-carrier:
1000 Btu/hr (70 cal/sec)
Fully loaded 3-carrier:
 1500 Btu/hr (105 cal/sec)
Power
Basic carrier: 117 VAC
60 Hz ± 5%  160 W
   5.4 amps
2-carrier:
 117 VAC
60 Hz ± 5%  320 W
 10.8 amps
3-carrier:
 117 VAC
60 Hz ± 5%  480 W
 16.2 amps
one properly grounded outlet needed for each carrier
Additional outlets may be needed if installing printers and PCs.
Temperature
40° through 104°F; 4° through 40°C 
(optimal temperature 60°F; 16°C)
Humidity
20% through 80% relative humidity
Ventilation
Allow at least 1 in. (2.5 cm) of space on the right and left sides of 
the control unit and 12 in. (30.5 cm) above and below the 
control unit to prevent overheating.