AUTOMATIC EXPANSION VALUE GT SERIES CABINETS
 
 
After the cabinet has been in operation for a short time the high pressure or discharge pressure of the 
refrigeration system should be 250 pisg to 270 pisg in a 75 
o
F ambient room.  The suction pressure at the 
compressor should be approximately 7 to 9 pisg *** .  The cabinet does not have to be at operation 
temperatures for the pressures to stabilize.  The automatic expansion valves are basically preset and should 
not need any adjustment for proper operation.  If the system pressures are not correct and the valve does 
need adjusting be aware that IN THE WORST CASE ONLY A VERY SMALL ADJUSTMENT MAY BE 
REQUIRED.  To increase the valve outlet pressure and thereby increase the suction pressure the adjusting 
screw is turned in a clockwise direction as the valve is viewed with the adjusting screw pointed up.  Be sure to 
replace the red plastic cap covering the valve adjustment screw.  After the pressure is set it SHOULD NOT 
TEND TO CHANGE after additional run time or as the cabinet temperature changes.  The sight glass, if install, 
may not appear to be completely full. This is a normal condition.  DO NOT INCREASE the refrigerant charge 
quantity above the listed charge because the sight glass does not show full. 
 
             *** Units used for boxed candy display should have the expansion valve adjusted to deliver 12     
                  to 14psig at compressor suction port, this pressure is not suitable for ice-cream. 
 
 
REFRIGERATION SYSTEM AND OPERATION 
 
The cabinet utilizes a Copeland Copelametric compressor and operates with refrigerant 404A.  Cabinet 
operates on 115/60/1 power.  The cabinet has a bare tube type condenser, which virtually eliminates the 
possibility of condenser blockage by dust and dirt.   
 
The cabinet operates with a specific charge of refrigerant 404A.  The amount of the charge of refrigerant is 
listed on the cabinet nameplate in ounces.  These systems use an automatic expansion valve to meter 
refrigerant to the evaporator.  They include automatic electric defrost systems which are time initiated (by the 
time clock) and terminated by a defrost termination thermostat which is mounted on a coil supporting bracket 
in the gravity coil section directly beneath the top of the cabinet.  This defrost termination overrides the time 
clock and turns the compressor back on line when the gravity coil is defrosted.  This is the point at which the 
coil has reached sufficient temperature to insure complete defrost.  If the defrost termination control should fail 
to operate, the time clock will automatically turn off defrost and again turn on the compressor after the 34 
minute (or the time interval you selected) interval set on the time clock.  If the time clock fails to turn the 
heaters off, a final back-up safety thermostat will shut off the heaters when gravity coil temperature reaches 
+80 
o
F.   
 
Cabinet has a refrigeration system known as automatic defrost gravity coil with cold wall construction.  This 
means the inner liner of the cabinet below the load level line is refrigerated by gravity flow of air from a fin and 
tube coil, as well as copper refrigerant lines attached to the back of the inner liner tank on all sides and the 
bottom.
 
 
CLEANING 
 
WARNING:  DO NOT REMOVE FROST WITH A KNIFE, PICK, OR SHARP OBJECTS.  DO NOT USE 
ABRASIVE CLEANERS OR CAUSTIC CLEANERS OR SCOURING PADS 
 
Every 30 to 60 days (depending on frost accumulation), the cabinet should be emptied, warmed up, and wiped 
down using a solution of 1 teaspoon of baking soda with 1 quart of water.  This solution will help eliminate 
odors.   Do not use strong soaps or detergents as they leave odors that can contaminate your product.  The 
GT line cabinets are equipped with a floor drain that exits out the lower rear of the cabinet.  This exit has a 
convenient garden hose fitting. 
If it is not convenient to turn the power off the cabinet, lay a piece of plastic sheeting on the floor of the cabinet 
and scrape the frost off walls using a plastic scraper.  Do not use metal scrapers.  This will damage the interior 
paint of the cabinet.