Справочник Пользователя для Carrier 30XW325-400

Скачать
Страница из 32
12
Dimensions
30XW UNIT DIMENSIONS
30XW UNIT AND WATERBOX DIMENSIONS
NOTES:
1.
Operating weight includes weight of water, refrigerent, and oil.
2.
 Denotes center of gravity.
3.
Dimensions shown in ft-in. [mm] unless noted.
4.
The recommended service clearance around the machine is 3 ft [914.4 mm].
5.
Victaulic nozzles are standard on all units. A flow switch can be factory-installed in evaporator inlet victaulic nozzle.
6.
Maximum fluid side pressure of condenser or evaporator is 150 psig [1034 kPa] (standard) or 300 psig [2068 kPa] (optional).
7.
Operating weight includes weight of water, refrigerant, and oil.
CONNECTIONS
PASSES
WATERBOX 
(EVAP/COND)
NOZZLE
TYPE
D
ft-in. [mm]
E
ft-in. [mm]
F
ft-in. [mm]
MAX UNIT OPERATING WEIGHT lb [kg]
325
350
400
Same Ends
2 Pass
NIH/NIH
Victaulic
13-3
3
/
4
 [4057]
3-11
3
/
8
 [1210]
6-6
11
/
16
 [1999]
14,319 [6495]
14,515 [6495]
14,759 [6695]
Flange
13-9
1
/
16
 [4193]
14,651 [6646]
14,847 [6646]
15,091 [6845]
NIH/MWB
Victaulic
13-11
5
/
8
 [4258]
14,498 [6576]
14,694 [6576]
14,938 [6776]
Flange
14,739 [6685]
14,935 [6685]
15,179 [6885]
MWB/NIH
Victaulic
14,489 [6572]
14,685 [6572]
14,929 [6772]
Flange
14,746 [6689]
14,768 [6689]
15,012 [6809]
MWB/MWB
Victaulic
14,668 [6653]
14,864 [6653]
15,108 [6853]
Flange
14,834 [6729]
15,030 [6729]
15,274 [6928]
Opposite Ends
NIH/NIH
Victaulic
13-6
5
/
16
 [4123]
3-11
3
/
8
 [1210]
6-6
11
/
16
 [1999]
14,319 [6495]
14,515 [6495]
14,759 [6695]
Flange
14-4
7
/
16
 [4380]
14,651 [6646]
14,847 [6646]
15,091 [6845]
NIH/MWB
Victaulic
14-2
3
/
16
 [4323]
14,498 [6576]
14,694 [6576]
14,938 [6776]
Flange
14-6
15
/
16
 [4443]
14,739 [6685]
14,935 [6685]
15,179 [6885]
MWB/NIH
Victaulic
14-2
13
/
16
 [4339]
14,489 [6572]
14,685 [6572]
14,929 [6772]
Flange
14-8
3
/
16
 [4475]
14,746 [6689]
14,768 [6689]
15,012 [6809]
MWB/MWB
Victaulic
14-10
11
/
16
 [4539]
14,668 [6653]
14,864 [6653]
15,108 [6853]
Flange
14,834 [6729]
15,030 [6729]
15,274 [6928]
1 or
3 Pass
NIH/NIH
Flange
14-5
5
/
8
 [4410]
14,828 [6726]
15,024 [6726]
15,268 [6925]
NIH/MWB
Flange
14-10
11
/
16
 [4539]
15,223 [6905]
14,768 [6896]
15,012 [6809]
MWB/NIH
Flange
15,244 [6915]
15,440 [6894]
15,684 [7114]
MWB/MWB
Flange
15,581 [7067]
15,777 [7063]
16,021 [7267]
SUCTION
END
DISCHARGE
END
EVAPORATOR
CONDENSER
SEE NIH CONDENSER
DETAIL FOR NOZZLE
MEASUREMENTS
SEE NIH EVAPORATOR
DETAIL FOR NOZZLE
MEASUREMENTS
MLV (OPTIONAL)
MLV (OPTIONAL)
a30-4745
STANDARD 30XW UNIT DIMENSIONS
NOTES:
1.
Weights shown for standard chiller (2 pass with NIH, victaulic waterboxes).
2.
See page 14 for unit mounting locations.
30XW UNIT 
SIZE
OPERATING 
WEIGHT, lb [kg]
MOUNTING LOCATION WEIGHT, lb [kg]
DIMENSIONS (ft-in. [mm])
1
2
3
4
A
B
C
325
14,319 [6495]
3734 [1694] 3828 [1736] 3337 [1514] 3420 [1551]
6-
3
/
8
  [1837]
6-
3
/
8
  [1837]
3
/
8
  [9.53]
350
14,515 [6584]
3785 [1717] 3880 [1760] 3383 [1535] 3467 [1573]
6-
3
/
8
  [1837]
6-
3
/
8
  [1837]
3
/
8
  [9.53]
400
14,759 [6695]
3848 [1745] 3946 [1790] 3439 [1560] 3526 [1599]
6-
3
/
8
  [1837]
6-
3
/
8
  [1837]
3
/
8
  [9.53]
LEGEND
MLV
— Minimum Load Valve
MWB — Marine Waterbox
NIH
— Nozzle-In-Head
SSV