8.6   Error Code and Error Message List
8.6.1   GOT error code list
*1
 When an error occurs, "FFH" is stored to the channel No.
804
The cable on the IN side 
is disconnected or is not 
connected.
Refer to explanations of SB0067 in the applicable network 
manual.
805
The cable on the OUT 
side is disconnected or is 
not connected.
Refer to explanations of SB0068 in the applicable network 
manual.
850
CC-Link switch setting 
error
• Check if the switch settings have no error.
• Check error codes stored in SW006A.
• Refer to explanations of SB006A in the applicable network 
manual.
851
Abnormal cyclic 
transmission status
• Check if terminating resistors are connected.
• Check error codes for the PLC CPU.
• Check the parameter for the PLC CPU on the master 
station.
• Check the error status of the master station.
• Refer to explanations of SB006E in the applicable network 
manual.
852 Abnormal host line status
• Check if the cable is unplugged or not.
• Refer to explanations of SB0090 in the applicable network 
manual.
853 Transient error
• Check the transient error occurrence status for each station 
stored in SW0094 to SW0097.
• Refer to explanations of SB0049 in the applicable network 
manual
Error 
code
Error message
Action
Channel 
No. 
storage