7.2  IEEE 1613 Type Tests 
 
IEEE Test  IEEE 1613 
Clause 
Description 
Test Levels 
Enclosure Contact 
+/- 8kV 
C37.90.3 9 
ESD 
Enclosure Air 
+/- 15kV 
C37.90.2 
Radiated RFI 
Enclosure ports 
35 V/m 
Signal ports 
+/- 4kV @ 2.5kHz 
D.C. Power ports 
+/- 4kV 
A.C. Power ports 
+/- 4kV 
C37.90.1 7  Fast 
Transient 
Earth ground ports 
+/- 4kV 
Signal ports 
2.5kV common mode @ 1MHz 
D.C. Power ports 
2.5kV common & differential mode @ 1MHz 
C37.90.1 7 
Oscillatory 
A.C. Power ports 
2.5kV common & differential mode @ 1MHz 
Signal ports 
5 kV (Failsafe Relay) 
D.C. Power ports 
5 kV 
C37.90 6  H.V. 
Impulse 
A.C. Power ports 
5 kV 
Signal ports 
2kV AC(Failsafe Relay) 
D.C. Power ports 
2kV AC 
C37.90 6 Dielectric 
Strength 
A.C. Power ports 
2kV AC 
Table 26 - IEEE 1613 Type Tests 
 
NOTE: 
•  If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur 
but recovery is automatic).  
•  If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will 
occur). 
 
 
7.3   IEC Environmental Type Tests 
 
Test 
Description 
Test Levels 
Severity 
Levels 
IEC 60068-2-1 
Cold Temperature 
Test Ad 
-40 deg. C, 16 Hours 
N/A 
IEC 60068-2-2 
Dry Heat 
Test Bd 
+85 deg. C, 16 Hours 
N/A 
IEC 60068-2-30 
Humidity (Damp Heat, 
Cyclic) 
Test Db 
95% (non-condensing), 55°C, 6 cycles 
N/A 
IEC 60255-21-1 
Vibration 
Tests Fc 
2g @ (10-150) Hz 
Class 2 
IEC 60255-21-2 
Shock 
Tests Ea 
30g @ 11 ms 
Class 2 
Table 27 - Environmental Type Tests