OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
MAINS 
f=60.0Hz 
U1=120V    U2=119V 
U3=121V
 
  1.  Mains input voltage information screen. 
2.  Mains input frequency. 
3.  Mains line voltage L1 (A) and L2 (B)phases. 
4.  Mains line voltage L3 (C) phase. 
 
 
RECTIFIER 
f=60.0Hz 
U1=120V    U2=119V 
U3=121V
 
  1.  Rectifier input voltage information screen. 
2.  Mains input frequency. 
3.  Input line voltage L1 (A) and L2 (B) phases. 
4.  Input line voltage L3 (C) phase. 
 
 
INVERTER: U1=120V 
U2=120V U3=120V 
Frequency = 60.0Hz 
Synchronized
 
  1.  Inverter voltage information screen. 
2.  Output inverter line voltage L1 (A), L2 (B) and L3 (C) phases 
3. Output 
frequency. 
4.  Synchronization status inverter with respect to mains. 
 
 
LOAD ON PHASE 
U1=120V I1=56A  50% 
U2=120V I2=50A  45% 
U3=120V I3=61A  55%
 
  1.  Load on output phases information screen. 
2.  Voltage, current and load percentage phase L1 (A). 
3.  Voltage, current and load percentage phase L2 (B). 
4.  Voltage, current and load percentage phase L3 (C). 
 
 
MISCELLANEOUS 
Battery Temp.  =  +25°C 
UPS Oper Time=  450h 
INV Oper 
Time=  430h
 
  1.  Screen informing about the battery and time of operation. 
2. Battery 
temperature. 
3.  Operating time (CPU powered) for the UPS (hours). 
4.   Operating time with inverter supplying the load (hours). 
 
 
MAINS FAULTS STAT. 
Minor = 
100 
Major = 
150 
Overloads =  
 
30
 
  1.  Screen informing about the quality of the input power. 
2.  The quantity of bypass mains out of tolerance faults. 
3.  The quantity of rectifier mains out of tolerance faults. 
4.  The total number of detected output overloads. 
 
 
IDENTIFICATION 
LP 33         40kVA  P1 
SW Version: 
x.x 
S/N: Q0040-0105-0001
 
  1.  Screen containing the data identifying the unit. 
2.  UPS family, nominal rating and for RPA: P + no. UPS. 
3.  The software version implemented on the control board. 
4.   The serial number of the unit. 
 
 
ECO Mode RATE 100% 
NR  FAST  TRANSIENT 
<2ms >2ms >5ms >10ms 
25 10 
7 3
 
  Screen containing the statistic evaluation in % (100= good; 0= bad) 
of the utility, for the ECO Mode operation. 
 
4.  The number of fast transients occurred on the bypass utility on 
the last seven days.