Справочник Пользователя для Emerson UPS Systems

Скачать
Страница из 36
Installation Drawings
23
Figure 16 Liebert NXL Maintenance Bypass Cabinet control wire diagram with interlock
WIRE DIAGRAM WITH INTERLOCK
  LOW VOLTAGE
TERMINAL STRIP
         - TB1 -
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
EPO PB SW
TB1-1
TB1-2
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
Connections at UPS External
Interface Board (EIB)
TB0820
TB0824
TB0813
TB0811
TB0821
02-806708
1
3
TB0820
TB0821
1 3
1
3
1
3
TB0811
TB0813
1
3
TB0824
TB1-3
Table 5
Control wiring connections with interlock
From
To
Purpose
TB1-1
Customer EPO
Push Button Switch
EPO Signal
TB1-2
Customer EPO
Push Button Switch
TB1-3
TB0821-2
Maintenance Bypass
Enable Contacts
TB1-4
TB0821-1
TB1-5
TB0824-3
UPS REPO Contacts
TB1-6
TB0824-2
TB1-7
TB0824-1
TB1-8
TB0811-3
MIB Contacts
TB1-9
TB0811-2
TB1-10
TB0811-1
TB1-11
TB0813-3
MBB Contacts
TB1-12
TB0813-2
TB1-13
TB0813-1
TB1-14
TB0820-2
EPO Status Contacts
TB1-15
TB0820-1
TB1-16
TB0820-3