Справочник Пользователя для Emerson MODBUS 485
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
58
Table 18
Liebert XDC
™
- Status and Coil
Controller
Liebert iCOM
®
v4
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Pump 1 Loss of Flow
10001
—
1
—
Active on Alarm
Pump 2 Loss of Flow
10002
—
1
—
Active on Alarm
Fan Issue
10003
—
1
—
Active on Alarm
System Condensation Detected
10004
—
1
—
Active on Alarm
Customer Input 1
10005
—
1
—
Active on Alarm
Supply Refrigerant Over Temp
10006
—
1
—
Active on Alarm
Supply Refrigerant Under Temp
10007
—
1
—
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10008
—
1
—
Active on Alarm
Ext Air Sensor A Over Temperature
10009
—
1
—
Active on Alarm
Ext Air Sensor A Under Temperature
10010
—
1
—
Active on Alarm
Ext Air Sensor A Issue
10011
—
1
—
Active on Alarm
Ext Air Sensor B Over Temperature
10012
—
1
—
Active on Alarm
Ext Air Sensor B Under Temperature
10013
—
1
—
Active on Alarm
Ext Air Sensor B Issue
10014
—
1
—
Active on Alarm
Ext Dew Point Over Temperature
10015
—
1
—
Active on Alarm
Pump Short Cycle
10016
—
1
—
Active on Alarm
Compressor 1A High Head Pressure
10017
—
1
—
Active on Alarm
Compressor 1B High Head Pressure
10018
—
1
—
Active on Alarm
Compressor 2A High Head Pressure
10019
—
1
—
Active on Alarm
Compressor 2B High Head Pressure
10020
—
1
—
Active on Alarm
Compressor 1A Short Cycle
10021
—
1
—
Active on Alarm
Compressor 1B Short Cycle
10022
—
1
—
Active on Alarm
Compressor 2A Short Cycle
10023
—
1
—
Active on Alarm
Compressor 2B Short Cycle
10024
—
1
—
Active on Alarm
Circuit 1 Low Suction Pressure
10025
—
1
—
Active on Alarm
Circuit 2 Low Suction Pressure
10026
—
1
—
Active on Alarm
Shutdown - Loss Of Power
10027
—
1
—
Active on Alarm
Smoke Detected
10028
—
1
—
Active on Alarm
Water Under Floor
10029
—
1
—
Active on Alarm
Service Required
10030
—
1
—
Active on Alarm