g
 
LP 5/6/8/10-11U installation drawings 
 
Model Heat 
dissipation 
Linear load 240 Volt 
Dimensions Air 
flow 
100% 
load 
Rel. 
humidity 
non-cond. 
Altitude 
(max 4000m) 
Input wiring 
Output wiring 
 
100% load 
50% load 
Weight 
 
 
Amb. 
temp. 
  
utility 
volt. 
120V 
utility volt. 
208V 
utility volt. 
240V 
output 
volt. 120V 
output 
volt. 208V 
output 
volt. 240V 
LP-U W 
Btu/hr 
Btu/hr 
Inch 
Inch 
Inch 
Lbs 
m3/hr 
°F 
  m 
AWG/mm
2
 AWG/mm
2
 AWG/mm
2
 AWG/mm
2
 AWG/mm
2
 AWG/mm
2
 
5-11 
571 1950 389 1329 26.8 12.3 28.7  295  660 14-104  <95 
N.A. 
10/6 
10/6 
8/10 
10/6 
10/6 
6-11 
661 2254 381 1300 26.8 12.3 28.7  295  660 14-104  <95 
N.A. 
8/10 
10/6 
8/10 
10/6 
10/6 
8-11 
948 3234 551 1882 26.8 12.3 28.7  386  660 14-104  <95 
N.A. 
6/14 
8/10 
6/14 
8/10 
8/10 
10-11 
1090 3719 556 1896 26.8 12.3 28.7  410  660 14-104  <95 
N.A. 
4/22 
6/14 
4/22 
8/10 
8/10 
5-11/120 
V  641 2187 425 1451 39.2 12.3 28.7  386  660 14-104  <95 
6/14 
N.A. 
N.A. 
8/10 
10/6 
10/6 
6-11/120 
V  744 2539 601 2051 39.2 12.3 28.7  386  660 14-104  <95 
<1000, derating 
12.5% per 1000 
4/22 N.A. N.A. 8/10 10/6 10/6 
 
Model 
Minimum free space required 
(Inches) 
front        side        rear 
Distance between mounting 
holes (Inches) 
Input overcurrent protection 
(AMPS) 
Output overcurrent protection (AMPS) 
LP-U 
 
 
 
z  120V 208V 240V 120V 
 
(1 X) 
120V 
(2X) 
208V 240V 
5-11 
 
4  2  8 7.24 
22.76 
7.48 
  35 30 40 20 25 20 
5-11 
/120V  4 2 8 
7.24 
22.76 
7.48 
60     40 
20 
25 20 
6-11 
4  2  8 7.24 
22.76 
7.48 
  40 35 50 25 30 25 
6-11 
/120V  4 2 8 
7.24 
22.76 
7.48 
70     50 
25 
30 25 
8-11 
4  2  8 7.24 
22.76 
7.48 
  60 45 70 35 40 35 
10-11 
4  2  8 7.24 
22.76 
7.48 
  70 60 80 40 50 40