Jumper Settings 
 
There are five jumper locations, which vary slightly depending on which network interface option is 
selected.  Their functions are as follows: 
 
JP1 SERVICE 
 
Momentarily shorting this jumper causes the Neuron chip to broadcast its Neuron ID across the 
network.  This jumper should normally be left open. 
 
Default: OPEN 
 
 
JP2 RESET 
 
Momentarily shorting this jumper asserts the –RESET signal on the Neuron chip.  This resets the 
LM104-P50, restarting any application program.  This jumper should normally be left open. 
 
Default: OPEN 
 
 
JP3 TERMINATION 
 
This jumper controls whether or not the onboard termination circuit is enabled or disabled. 
 
 
Shorted 
Termination is enabled. 
 Open 
 Termination 
is 
disabled. 
 
Please see page 7, “Cable Grounding and Termination”  regarding termination issues. 
 
Default: 
OPEN (no termination) 
 
 
JP4 I/O 
ADDRESS 
 
This jumper selects the I/O address range used by the LM104-P50: 
 
Position 1 
Address &h1E0-&h1EF 
Position 2 
Address &h300-&h30F 
Position 3 
Address &h310-&h31F 
Position 4 
Address &h320-&h32F 
 
Default: 
Position 1 (&h1E0-&h1EF)