TROUBLESHOOTING
CHAPTER8 TROUBLESHOOTING
This chapter explains how to check the data link status and error details.
(1) For the master station
(a) Connect GX Developer to identify a faulty part.
(b) Use the special relay (for link) or special register (for link) of a CPU module to 
identify a faulty part.
Type MELSECNET, MELSECNET/B Data Link System Reference Manual
(c) When the master station is faulty, check the error with the ERROR LED.
(2) For Q series local stations
(a) Data of the special relay (for link) and special register (for link) of a local module 
are refreshed into CPU module devices.
The faulty part can be checked by using the refreshed devices.
         
Note that the network diagnostics of GX Developer is not available for Q series 
local stations. Check the fault by the above method.
(b) When a Q series local station is faulty, check the error with the ERROR LED that 
is lit.
(c) Check for proper cable connection.(
1) In the MELSECNET data link system, are the slave stations connected in order 
of station No. starting from the master station (01 
 02 
 n (n
64)) in the 
forward loop direction?
2) Isn't any station No. skipped in the setting?
3) Isn't any station No. duplicated in the same tier?
(d) Check the program for refresh and for receiving LRDP/LWTP instruction.