3.1 Performance Specifications
 
3
SPECIFICATIONS
CHAPTER3 SPECIFICATIONS
This chapter describes performance specifications and function list of a local module.
For general specifications, refer to the following manual.
User's manual for the CPU module used (Hardware Design, Maintenance and 
Inspection)  
3.1
Performance Specifications
This section describes the performance specifications of the MELSECNET or 
MELSECNET/B data link system and the local module.
(1) Performance specifications of MELSECNET data link system and 
A1SJ71AP23Q
 * 1 Connecting an optical fiber cable with a connector requires professional skills and special tools. 
Also, a connector dedicated to an optical fiber cable is required.
For purchase, contact your local Mitsubishi Electric System Service or representative.
Table 3.1 Performance specifications of MELSECNET data link system and A1SJ71AP23Q
Item
Specifications
MELSECNET data link system
MELSECNET mode 
MELSECNET II mode
MELSECNET II composite 
mode
Maximum applicable 
link points per station
Input (X)
Up to the maximum number of I/O points for the CPU module used in the master station is 
applicable.
(The total number of link points for slave station is equal to the number of link using points for the 
master station)
Output (Y)
Maximum link points 
in a system
Link relay (B)
1024 points (128 byte)
4096 points (512 byte)
Link register 
(W)
1024 points (2048 byte)
4096 points (8192 byte)
Maximum link points 
per station
Master station
1024 byte
1024 byte (First half of link parameters)
1024 byte (Latter half of link parameters)
Local station
Remote I/O 
station
512 byte
Number of I/O points: 512 
points
-
512 byte
Number of I/O points: 512 
points
Communication speed
1.25Mbps
Communication method
Half duplex bit serial method
Synchronization method
Frame synchronization method
Transmission path
Duplex loop
Overall cable distance
Up to 10km (Station-to-station 1km)
Number of connected stations
Up to 65 (Master station: 1, The total number of local stations and remote I/O stations: 64)
Modulation method
CMI method
Transmission format
Conforming to HDLC (Frame format)
Error control system
Retries due to CRC (generating polynomial X
16 
+ X
12 
+ X
+1) and time out
RAS function
•Loopback function due to error detection and cable break
•Diagnostic function including link line check of host station etc.
Connector
2-core optical connector plug (User prepared
*1
)
Applicable cable
Optical fiber cable (User prepared
*1
)
Number of I/O occupied points
32 points (Intelli: 32 points)
Internal current consumption (5VDC)
0.33A
Weight
0.30kg