Справочник Пользователя для Motorola 3460
![Motorola](https://files.manualsbrain.com/attachments/83de88ba2280e7232128e8931d7cbd2a38dcc654/common/fit/150/50/0293f422c4d32e7e0f777d5e11bc33c83ea5627f71ddf155374c02a23d9a/brand_logo.png)
3460 Fast’R
1-12
Fan and Deflector Requirements
Forced-air cooling for up to four rack-mounted enclosures can be
provided by fans and a deflector, mounted below the enclosures, to
provide passive, bottom-entry rear exhaust and upward-forced, front-
entry cooling air. Refer to Figure 1-6. The airflow requirement is 80
CFM (2266230 CCM).
provided by fans and a deflector, mounted below the enclosures, to
provide passive, bottom-entry rear exhaust and upward-forced, front-
entry cooling air. Refer to Figure 1-6. The airflow requirement is 80
CFM (2266230 CCM).
For example, three fans rated 117 CFM (202176 CCM) at a static
pressure of 0 inches of water provide enough airflow, when cooling four
enclosures. The deflector ensures that hot air from equipment below the
enclosures does not mix with enclosure-cooling air. The cabinet must
have venting at the top or rear to let exhaust air escape.
pressure of 0 inches of water provide enough airflow, when cooling four
enclosures. The deflector ensures that hot air from equipment below the
enclosures does not mix with enclosure-cooling air. The cabinet must
have venting at the top or rear to let exhaust air escape.
Figure 1-6. Cabinet Arrangement
—
Three or More Enclosures
Unit 2
Fan Chassis 2
Unit 1
Fan Chassis 1
AccessWay
AccessWay
AccessWay
AccessWay