Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series 
Revision January, 2008, Doc. Name: 2007PDD23000007 
 
 
1-107 
Modicon TSX Micro (Modbus RTU) 
A. HMI factory settings 
Baud rate: 9600, 8, ODD, 1. 
Controller station number: 2. 
Control area/status area: %MW0 / %MW10. 
NOTE
 
1)  HMI must select Modbus (Master) --- 984 RTU as the communication mode. 
2)  The communication mode of PLC should be switched to Modbus Slave by using PL7 software.  
B. Connections (Connector Pinouts) 
RS-485 
DOP 
9 pin D-SUB male (RS-485) 
Controller 
8 pin Mini DIN male (RS-485) 
Controller 
8 pin Mini DIN male 
(RS-485) 
R XD +  ( 2)
(1 ) D+
TXD+ (3)
R XD -  (1 )
TXD- (4)
(2 ) D-
(5 )
(7 )
 
 
 
 
 
 
 