Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-12  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Delta DVP PLC 
A. HMI factory settings 
Baud rate: 9600, 7, Even, 1. 
Controller station number: 1. 
Control area/status area: D0 / D10. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
X_Data 
Xn 
n: 0 ~ 360(octal) 
N/A 
Y_Data 
Yn 
n: 0 ~ 360(octal) 
N/A 
M_Data 
Mn 
n: 0 ~ 1520, 1536 ~ 4080 
N/A 
S_Data 
Sn 
n: 0 ~ 1008 
N/A 
T_Register 
Tn 
n: 0 ~ 255 
N/A 
C_Register 
Cn 
n: 0 ~ 199 
N/A 
D_Register 
Dn 
n: 0 ~ 4095, 4096 ~ 9999 
N/A 
HC_Register 
Cn 
n: 200 ~ 255 
N/A 
NOTE
 
1)  (W) is “Word”. 
2)  (DW) is “Double Word”. 
3)  X_Data / Y_Data / M_Data / S_Data: Address must be 0 or the multiple of 16.  
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
X_Data 
Xn 
N/A 
n: 0 ~ 377(octal) 
Y_Data 
Yn 
N/A 
n: 0 ~ 377(octal) 
M_Data 
Mn 
N/A 
n: 0 ~ 1520, 1536 ~ 4080
S_Data 
Sn 
N/A 
n: 0 ~ 1023 
T_Coil 
Tn 
N/A 
n: 0 ~ 255 
C_Coil 
Cn 
N/A 
n: 0 ~ 255