Справочник Пользователя для Phoenix MINI-PS-100-240AC/24DC/1.3 2866446

Модели
2866446
Скачать
Страница из 6
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
PHOENIX CONTACT GmbH & Co. KG
Page 2 / 6
http://www.phoenixcontact.com
Jun 4, 2008
An international approval package including UL 60950 for information technology equipment and UL 508 for industrial
regulating devices pave the way for worldwide applications.
Technical data
Input data
Nominal input voltage
100 V AC ... 240 V AC
AC input voltage range
85 V AC ... 264 V AC
DC input voltage range
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
DC frequency range
0 Hz
Current consumption
Approx. 0.6 A (120 V AC)
0.4 A (230 V AC)
Inrush surge current
< 15 A (< 0.6 A2s)
Power failure bypass
> 40 ms (120 V AC)
> 100 ms (230 V AC)
Input fuse
1.25 A (slow-blow, internal)
Recommended backup fuse
6 A
10 A
16 A (characteristic B)
Name of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
22.5 V DC ... 28.5 V DC (> 24 V constant capacity)
Output current
1.3 A (-25°C ... 70°C)
1.6 A (with POWER BOOST, < 40°C permanent)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
No
Starting delay with capacitive load
(Unrestricted)
Max. capacitive load
Unlimited
Current limitation
Approx. 5 A (for short circuit)
Control deviation
< 1 % (change in load, static 10% ... 90%)
< 3 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mVPP
Peak switching voltages nominal load
< 50 mVPP