CHAPTER 5 ACCESS BETWEEN CPU MODULES AND OTHER MODULES
5
5.2  Acce
ss to Non-
co
ntrolled
 Module
s
5.2.1  L
oadin
g inpu
t (X) da
ta
5.2.1
Loading input (X) data
Data in the input (X) of input modules and intelligent function modules controlled by other CPU modules can be loaded 
in accordance with the "I/O Sharing When Using Multiple CPUs" setting in PLC parameter ("Multiple CPU Setting").
(1) When the "All CPUs Can Read All Inputs" checkbox is checked
The on/off data of input modules and intelligent function modules controlled by other CPU modules can be 
loaded. The on/off data are loaded during input refresh processing before the program operation starts.
The on/off data can also be loaded by using the direct access input (DX).
I/O Sharing When Using Multiple CPUs
     All CPUs Can Read All Inputs:
     Input data can be loaded from the modules 
     controlled by other CPU modules.
     All CPUs Can Read All Inputs:
     Input data cannot be loaded from the modules 
     controlled by other CPU modules.
X0 to XF
Y10 to 
Y1F
X20 to X2F
Y30 to 
Y3F
Input Output Input Output
Point assigned 
to each slot
16
16
16
16
2
2
Control CPU setting
2
On/off data can be loaded from modules controlled 
by another control CPU.
On/off data can 
loaded by the 
direct access input.
On/off data 
can loaded 
by input refresh.
X20
DX20
Slot number
CPU
0
1
2
3
4