CHAPTER 11
TROUBLESHOOTING
This chapter describes errors that may occur while using the high-speed counter module, and those troubleshooting.
The high-speed counter module does not support the following functions performed in the system monitor.
• Display of the "H/W Information" window
• Display of errors and the corresponding actions in the "Module's Detailed Information" window
• Module error collection function
11.1
Error Information
(1) Checking errors in the system monitor
[Diagnostics] 
 [System Monitor]
(2) Error information that the high-speed counter module detects
Description and cause
Where to check the error information
Action
Overflow error
• In linear counter, an up pulse has 
been counted from the present 
value 2147483647.
• In linear counter, a down pulse has 
been counted from the present 
value -2147483648.
Module status display in the system monitor window
• No display: No overflow detected (no error)
• Module error: Overflow detected
Execute a preset to clear the overflow error.
Overflow detection flag
The following value is stored in CH Overflow 
detection (Un\G8, Un\G40).
• 0: No overflow detected
• 1: Overflow detected
Module error status bit of the module information 
read by the UNIRD instruction
• 00: No overflow detected (no error)
• 10: Overflow detected (moderate error)
An icon showing a moderate error is 
displayed if an overflow error is detected.