CHAPTER 7 SETTINGS
7
7.
3 I
nt
elli
gen
t F
unc
tion Module Det
ailed Set
ting
7.3
Intelligent Function Module Detailed Setting
Perform an output mode setting for an error and CPU module operation mode setting for a hardware error.
(1) Setting method
Open the "I/O Assignment" tab.
1.
Open "I/O Assignment" of the PLC parameter.
Project window 
 [Parameter] 
 [PLC 
Parameter]  
[I/O 
Assignment]
2.
Click the 
 button.
3.
Select "Clear" or "Hold" for "Error Time Output 
Mode".
4.
Select "Stop" or "Continue" for "PLC Operation 
Mode at H/W Error".
5.
Click the 
 button to complete the settings 
of "Error Time Output Mode" and "PLC Operation 
Mode at H/W Error".
Item
Description
Setting value
Remarks
Error Time Output 
Mode
Select whether to clear or hold module 
output if a CPU stop error occurs.
• Clear (default)
• Hold
• Clear: If a CPU stop error occurs, all 
external outputs of coincidence 
signals turn off.
• Hold: If a CPU stop error occurs, 
external outputs of coincidence 
signals are held in the status before 
the CPU module stops.
PLC Operation Mode 
at H/W Error
• Select whether to stop or continue the 
CPU module operation if a high-speed 
counter module error (SP.UNIT DOWN) 
is detected.
• The error (SP.UNIT DOWN) is detected 
if the module READY flag is not in ready 
due to module hardware failure.
• Stop (default)
• Continue
• Stop: If a high-speed counter module 
error is detected, the CPU module 
stops.
• Continue: Even if a high-speed 
counter module error is detected, the 
CPU module continues running a 
program for modules other than the 
faulty one.