Instruction Manual
IM-106-4050 Original Issue
March 2006
OxyBalance Oxygen Display 
and Averaging System
SYSTEM OVERVIEW
General
The OxyBalance is a display and averaging system that augments the 
Oxymitter O
2
 probe product line. It receives up to (8) 4-20 mA signals from 
Rosemount, Westinghouse, or other O
2
 probes, and calculates and transmits 
up to 4 additional programmable averages (again 4-20 mA). The OxyBalance 
system also displays the individual and averaged outputs on a color touch 
screen graphic panel. Trend screens, bar graphs (individual probes only), and 
alarming indications are provided when a probe goes off line.
The OxyBalance system replaces much of the functionality of older averaging 
systems offered by Westinghouse and Rosemount - the Control Room 
Electronics (CRE), 1500 Controller-based averaging systems, and the 
Veritrak-based 1290 systems. It should be noted, however, that the heater 
control and signal conditioning for each individual probe is executed within 
separate electronics for each probe. Unlike past averaging systems, and most 
current competitive averaging systems, there is no component failure in the 
OxyBalance system that will cause the loss of individual probe signals.
The OxyBalance system senses 4-20 mA inputs automatically. Averages are 
very easy to set up. Any probes that may fail will default to a 3.5 mA signal 
level, indicate in red, and the OxyBalance system will remove these probes 
from the average. Likewise, probes that are in calibration will indicate blue, 
and provide a contact closure to the OxyBalance system to remove them from 
the average while calibrating.
Trends offer adjustable scaling, three time spans (5 min., 8 hrs., and 24 hrs.), 
and panning capability back and forth in history.
OxyBalance System 
Features
The standard OxyBalance system includes the following features:
• Graphically displays and trends from 1 to 8 O
measurements.
• Probe inputs may be from Rosemount Analytical, Westinghouse or any 
competitive O
2
 probe with a 4-20 mA signal output.
• Generates up to four 4-20 mA signals as programmable averages.
• Failed or calibrating probes are automatically removed from the 
average
• Individual probe readings remain autonomous and are unaffected by 
any potential failure of the OxyBalance system.
• Variable time scale trends for each individual probe value, as well as for 
up to 4 averages.
• Password protection for set up menus.