Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
4 - 24 
4   FUNCTIONS 
MELSEC-QnA 
 
4.8 Data Link Status Setting When the Master Station Programmable Controller CPU Has 
an Error 
The data link status for when the master station's programmable controller CPU has 
an "operation-stop error" can be set. 
The data link between local stations can be continued. 
 
POINT 
 
Even if the master station programmable controller CPU has an "operation-stop error", the 
data link continues. 
 
[Setting method] 
Set to the "operation specification when the CPU is down (address 6
H
)" in the 
parameter information area of the master station's buffer memory 
0......Stop (default) 
1......Continue