4 - 27 
4   FUNCTIONS 
MELSEC-QnA 
 
4.11 Data Link Stop/Restart 
The data link in the host station can be stopped or restarted. 
When the data link is stopped for the master station, the data link for the entire system 
stops. 
 
(1)   The link special relay used in the program is shown below: 
SB0000: Data link restart request 
SB0002: Data link stop request 
SB0041: Data link restart complete 
SB0045: Data link stop complete 
 
(2)   A program example to stop/restart the data link is shown below. 
This example assumes that the module's first I/O No. is X/Y30. 
1
 Relationship between the programmable controller CPU and master station 
 
Programmable controller CPU
M15 M0
to
M35
M20
to
TO
FROM
Master station
Link special relay (SB)
SB000F
SB0000
to
SB004F
SB0040
to
5E0
H
5E4
H
 
 
2
 Program example 
 
M0
Data link stop 
Data link restart 
Restart command 
M21 (SB0041)
FROM H0003 H05E4 K4M20 K1
Read SB0040 to SB004F 
status 
M2 (SB0002) data-link  
stop on 
M2 (SB0002) data-link  
stop off 
M0 (SB0000) data-link  
restart on 
Write to SB0000 to SB000F
SM400
Stop command 
SET M2
M25 (SB0045)
SET M2
RST M2
SET
SET
RST M0
TO
H0003 H05E0 K4M0
K1
SM400
M0 (SB0000) data-link 
restart off 
 
 
POINT 
 
SB0000 must be used to start a data link if it has been stopped with SB0002.