7 - 7 
7   DATA LINK PROCEDURE 
MELSEC-QnA 
 
No. Name 
Description 
Sets the operation condition (setting at shipment: All is OFF) 
Setting valid/not valid 
Number 
Setting detail 
Description 
x
 Master 
station 
x
 Standby 
master 
station in 
controlling 
the 
system 
x
 Local 
station 
x
 Standby 
master 
station on 
standby 
SW1 
Station type 
OFF : Master station/Local station 
ON   : Standby master station 
(Valid) (Valid) 
SW2 
(Unusable) Always 
off – 
– 
SW3 
(Unusable) Always 
off – 
– 
SW4 
Input data status of the 
data link error station 
OFF : Clear 
ON   : Hold 
Valid Valid 
Number of 
occupied stations
SW5 SW6 
– 
– 
1 station 
OFF 
OFF 
2 stations 3 OFF ON 
3 stations 3 ON ON 
SW5 
SW6 
Number of occupied 
station 
4 stations 
ON 
OFF 
Invalid Valid 
SW7 
(Unusable) Always 
off – 
– 
5
  Condition setting switch 
AJ61QBT11 
ON
OFF
S  MST
M / L
HOLD
CLEAR
3/4
1/2
SW
1
2
3
4
5
6
7
8
ON
1/4
2/3
 
A1SJ61QBT11 
12
34
56
78
O N
1
2
3
4
5
6
7
8
M / L
CLR
1/2
S. N
HLD
3/4
SW OFF
ON
1/4
2/3
 
SW8 
(Unusable) Always 
off – 
– 
6
  Terminal block 
10
8
6
4
2
9
7
5
3
1
NC
DA
NC
(FG)
SLD
NC
NC
NC
DB
DG
 
Connect the CC-Link dedicated cable for data link. 
Refer to Section 7.5 for how to connect the cables. 
 
Note that the following terminals are connected inside of the module. 
 
SLD (terminal No.8) — FG (terminal No.10) 
NC (terminal No.7) — NC (terminal No.9) 
 
2-piece type terminal block. The module can be exchanged with another without removing 
the signal lines from the terminal block. (Replace the module after turning off its power.) 
3 The AJ61QBT11 of hardware version F or later and the A1SJ61QBT11 of hardware version G or later are compatible with this setting. 
For other than the above, only SW5 is used to set the number of occupied stations. 
OFF: 1 station occupied 
ON  : 4 stations occupied 
Keep SW6 OFF as it is unusable. 
 
POINT 
 
The setting of switches 
2
 to 
5
 become valid after the module power supply is turned on from 
off or after the programmable controller CPU is reset. 
When the setting is changed while the module power supply is on, turn off and then on the 
module power supply or reset the programmable controller CPU again. 
 
Important 
 
Do not use station number 64 in a system where the standby master station exists. 
When it is used, the station number 64 will not communicate correctly.