7.6.2 T-Branch communication specifications list 
The following describes the communication specifications for T branch connection.  
For communication specifications not listed below, see Section 3.2. 
 
Item Specification 
Remarks 
Transmission speed 
625 kbps 
156 kbps 
10 Mbps, 5 Mbps, and 2.5 Mbps are not allowed.
Maximum length of the main line 
100 m (328.1 ft.) 
500 m (1640.5 ft.) 
Indicates the length of the cable between 
terminating resistors. The length of the T branch 
cable (branch line length) is not included. 
Maximum length of the branch line 
8 m (26.25 ft.) 
Indicates the overall cable length per branch. 
Overall branch line length 
50 m (164.05 ft.) 
200 m (656.2 ft.) 
Indicates the overall length of the entire branch 
cable. 
Maximum number of connected 
modules on the branch line 
6 stations per branch 
The total number of connected stations depends 
on the CC-Link specifications. 
Connection cable 
CC-Link dedicated cable  
Version 1.10 compatible CC-Link dedicated cable 
• The CC-Link dedicated high-performance cable 
cannot be used. 
• 
Mixing of different brands of CC-Link 
dedicated cables is not allowed. 
• 
 Mixing of different brands of Ver. 1.10 
compatible CC-Link dedicated cables is 
allowed.
  
When the hardware version of the master module is as 
follows:  
AJ61BT11 
: Hardware version D or later 
AJ61QBT11 
: Hardware version D or later 
A1SJ61BT11  : Hardware version E or later 
A1SJ61QBT11 : Hardware version E or later 
 
Connect the 110
Ω
 terminating 
resistor
 supplied with the 
master module. 
For connecting, refer to Section 7.5. 
• The method of connecting terminating resistors 
across DA and DG, and across DB and DG can 
be used. 
Terminating resistor  
(connection method) 
When the hardware version of the master module is other 
than above: 
110 
Ω ± 5 %, 1/2 W × 4 
(Connect across DA and DG, and across DB and DG) 
….both ends 
 
[Connection] 
DA
DB
DG
SLD
FG
110
110
 
• Use a commercially available terminating resistor 
of 110 
Ω ± 5 % and 1/2 W resistance. 
• 110 
Ω and 130 Ω terminating resistors supplied 
with the master/local modules cannot be used. 
T branch terminal block/connector 
• Terminal block: Off-the-shelf terminal block 
• Connector: Connector for FA sensor (ICE947-5-2) 
comparable product is recommended 
• When wiring cables for the main line side, try 
not to remove the covering as much as 
possible.