Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
8 - 15 
8   PROGRAMMING 
MELSEC-QnA 
 
Table 8.1 Link special relay list (continued) 
 
Availability  
(  : available,  
   : not available ) 
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SB0073 
Operation specification 
when CPU is down status 
Indicates specification when CPU is down status by parameter. 
OFF : Stop 
ON : 
Continue 
 
 
 
SB0074 
Reserved station specified 
status 
Indicates the reserved station specified status by parameters 
(SW0074 to SW0077). 
OFF  : No specification 
ON : 
Specification 
exists 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Reserved 
station specified status (SW0074 to SW0077). 
 
 
 
SB0075 
Error invalid station 
specified status 
Indicates the error invalid station specified status by parameters 
(SW0078 to SW007B). 
OFF  : No specification 
ON : 
Specification 
exists 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Error invalid 
station specified status (SW0078 to SW007B). 
 
 
 
SB0076 1 
Temporary error invalid 
station setting information 
Indicates the setting of yes/no for temporary error invalid station. 
OFF : No 
ON : 
Yes 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Temporary error 
invalid station specified status (SW007C to SW007F). 
 
 
 
SB0077 Parameter 
receive 
status 
Indicates the parameter receive status from the master station. 
OFF  : Receive complete 
ON  : Receive not complete 
 
 
 
SB0078 1 
Host station switch 
change 
Detects the setting switch change of the host station during data link. 
OFF  : Not change 
ON : 
Change 
 
 
 
SB0080 
Other station's data link 
status 
Indicates the communication status of the other stations.  
(SW0080 to SW0083). 
OFF  : All stations normal 
ON  : Faulty station exists 
It takes maximum of six seconds for this relay to turn on after a slave 
station connected to the master station or local station becomes 
faulty. 
 
 
 
SB0081 1 
Other station watchdog 
timer error status 
Indicates the watch dog timer error occurrence status in the other 
station (SW0084 to SW0087). 
OFF : No error 
ON : 
Error 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Other station 
watchdog timer error occurrence status (SW0084 to SW0087). 
 
 
 
SB0082 1 
Other station fuse blown 
status 
Indicates the fuse blow occurrence status in the other station 
(SW0088 to SW008B). 
OFF  : Not blown 
ON : 
Blown 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Other station 
fuse blown status (SW0088 to SW008B). 
 
 
 
SB0083 1 
Other station switch 
change status 
Detects the setting switch change of the other station during data link. 
OFF  : Not change 
ON : 
Change 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Other station 
switch change status (SW008C to SW008F). 
 
 
 
SB0090 
Host line status 
Indicates the hot station line status. 
OFF : Normal 
ON : 
Error 
(disconnection) 
 
 
 
1: Link special relay added to the function version B or later