Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
9 - 8 
9   COMMUNICATION BETWEEN THE MASTER STATION AND THE 
REMOTE I/O STATION 
MELSEC-QnA 
 
X0040 X004F
SM400
SM400
Read the remote input 
(RX) 
For communicating
with AJ65BTB1-16D
(Station No.1)
X0041
N0
M500
MC
Master station is performing
the data link.
M500
N0
K4M401 K1
FROM H0004 H0680
Read each station's data
link status (SW0080) 
M401
Remote I/O station
(station No.1) is in error. 
YD0
M402
Remote I/O station
(station No.2) is in error. 
YD1
M403
Remote I/O station
(station No.3) is in error. 
YD2
M404
Remote I/O station
(station No.4) is in error. 
YD3
M405
Remote I/O station
(station No.5) is in error. 
YD4
K4M0 K9
FROM H0004 H00E0
M0
Y20
M15
Y2F
When input (X00 to X0F)
of AJ65BTB1-16D is 
turned on, Y20 to Y2F 
of the master station 
AY41 is turned on. 
to
For communicating
with AJ65BTC1-32D
(Station No.2) 
M32
YA0
M63
YBF
When input (X00 to X1F)
of AJ65BTC1-32D is 
turned on, YA0 to YBF 
of the master station
AY42 is turned on. 
to
For communicating
with AJ65BTB1-16T
(Station No.3)
X10
M200
X1F
M215
When X10 to X1F of the 
master station AX41 is 
turned on, output (Y00 to
Y0F) of  AJ65BTB1-16T 
is turned on.  
to