12 - 16 
MELSEC-QnA 
12   COMMUNICATION IN THE COMPOUND SYSTEM 
 
12.3.2 Confirming the operation by the program 
Confirm if the data link can be performed normally using a sequence program. 
 
1
 When X00 of the remote I/O station is turned on, Y20 of the master station is turned 
on. 
2
 When X10 of the master station is turned on, Y08 of the remote I/O station is turned 
on. 
3
 The digital value which was converted by the remote device station is stored in 
D210 (CH1) and D211 (CH2) of the master station and the local station. 
4
 When M160 of the master station is turned on, M160 of the local station is turned 
on. 
5
 When the data is written into D100 of the master station, it is stored in D100 of the 
local station. 
6
 When M60 of the local station is turned on, M60 of the master station is turned on. 
7
 When the data is written into D310 of the local station, it is stored in D310 of the 
master station. 
 
AY42
AX42
AJ61
QBT11
AY41
Y20
AX41
X10
Q3ACPU
A62P
Master station
Terminating resistor
 I/O module
AJ65BTB1-16DT
ON
1
ON
2
ON
1
2
Y08
X00
ON
Remote device station 
(station No.2: occupies 2 stations)
A/D conversion module
AJ65BT-64AD
Remote I/O station 
(station No.1: occupies 1 station)
A/D conversion by AJ65BT-64AD
CH1 digital value
D210
CH2 digital value
D211
3
AY41
Y60
Y7F
to
AX41
X40
X5F
to
AJ61
QBT11
X/Y00
X/Y1F
to
AX40
X20
X2F
to
Q3ACPU
A62P
AY40
Y30
Y3F
to
Local station 
(station No.4: occupies 1 station)
3
Terminating resistor