Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
13 - 5 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
Complete
From the previous page
From the previous page
From the previous page
Is the "L RUN"
LED on? 
Is the "SD" LED
on (flashing)?
Y
N
Is the "SD" LED
on (flashing)?
Is the baud rate
setting correct?
Malfunction of the
corresponding  
module
Set the baud  
rate correctly.
Reset the power supply/ 
press the reset switch.
Is the  
communication cable
wired correctly?  
 1
Wire the communication
cable correctly.
Malfunction of the  
corresponding module
(Baud rate switch)
Is the  
station number  
switch correctly set (not
overlapping with other  
stations)?
Malfunction of the  
corresponding module 
(Station number switch)
Set the station  
number correctly.
Reset the power supply/ 
press the reset switch.
Are the  
station number  
switches set correctly (not
overlapping with other  
stations)?
Set the station  
number correctly.
Malfunction of the  
corresponding module 
(Station number switch)
Reset the power supply/ 
press the reset switch.
Y
N
Y
N
Y
N
Y
N
Y
N
Y
N
 
 
1 Check for a short, reversed connection, wire breakage, terminating resistor, FG connection, overall distance and 
station-to-station distance.