15 - 1 
MELSEC-QnA 
15   FUNCTIONS (FUNCTION VERSION B OR LATER) 
 
 
 
 
 
 
 
 
 15
 
 
 
 
 
 
 
 
 
 
 
 
 
15. FUNCTIONS (FUNCTION VERSION B OR LATER) 
The functions added in the function version B or later are explained. 
 
15.1 List of Functions 
A list of functions is shown in Table 15.1. 
 
Table 15.1 List of functions 
Availability of functions 
Item Function 
overview 
Reference 
section 
Master 
station 
Local 
station 
Standby 
master 
station 
Parameter registration 
function 
Sets parameters from a peripheral device as a part of CPU 
parameters. The following two parameters are available: 
• Network parameters 
• Automatic refresh parameters 
Section 
15.2 
 
Automatic refresh 
function 
Cyclic transmission data, such as RX and RY, can be refreshed to a 
desired device by the END processing, using the software package 
( 2). 
Section 
15.3 
 
 
 
Synchronous 
mode 
Data link can be performed using the scan 
synchronized with the sequence program. 
Section 
15.4 
 
 
 
Scan synchronous 
function 
Asynchronous 
mode 
Data link can be performed using the scan not 
synchronized with the sequence program. 
Section 
15.4 
 
 
 
Standby master 
function 
Data link can be continued when an error occurs at the master 
station, by switching to the standby master station. 
Section 
15.5 
 
 
 
Transient transmission can be performed to the intelligent device and 
local stations using dedicated instructions. 
Dedicated instructions also facilitate read/write of data with 
handshake from/to remote devices. 
Section 
15.6 
 
 
 
Dedicated instructions 
Device read/write with respect to the CPU in the specified station is 
possible using dedicated instructions. 
Section 
15.6 
Communication 
instruction 
Data communication with other stations is possible. 
Data read/write with other stations is also possible. 
Section 
15.7 
 
2 3 
 
2 3 
 
2 3 
Remote I/O net mode 
Communication can be performed only with the remote I/O station 
without setting parameters. 
Section 
15.8 
 
 
Temporary error 
invalid station 
specification function 
Replacement of modules can be performed online without detecting 
an error at the corresponding remote station. 
Section 
15.9 
 
 
 
Online test function 
Line testing and control of link such as starting up and stopping can 
be performed from a peripheral device. 
Section 
15.10 
 
 
 
Monitor/diagnosis 
function 
Monitoring and diagnosing can be performed from a peripheral 
device. 
Section 
15.11 
 
 
 
 
1 Network parameter setting is not necessary. 
2 It can be used with software version J (manufactured in Jan., 1998) and later. 
3 The CPU of the specified station can only be used with QnACPU. 
4 Available with software version P (manufactured in Sep., 1998) or later. 
 
15.2 Parameter Registration Function 
This function sets parameters as a part of CPU parameters from a peripheral device, 
using SW IVD/SW NX-GPPQ/GX Developer. There are two types of parameters: 
network parameter and automatic refresh parameter. 
For SW IVD/SW NX-GPPQ/GX Developer, refer to the operating manual supplied 
with the product. 
 
POINT 
 
• The parameter registration function is effective only up to eight master modules. When using 
nine or more master modules, it must be done from the sequence program. 
• The "Y" at the master module will be ignored while using the parameter registration function.