2 - 1 
2   SYSTEM CONFIGURATION 
MELSEC-QnA 
 
 
 2
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2. SYSTEM CONFIGURATION 
The system configuration for the CC-Link is described in this chapter. 
 
2.1 Total Configuration 
A total of 64 remote I/O stations, remote device stations, or local stations can be 
connected for one master station. 
However, the following conditions must be satisfied: 
 
(1) {(1×a)+(2×b)+(3×c)+(4×d)}   64 
  a : Number of modules occupying 1 station  c : Number of modules occupying 3 stations 
  b : Number of modules occupying 2 stations  d : Number of modules occupying 4 stations 
   
(2) {(16×A)+(54×B)+(88×C)}   2304 
  A : Number of remote I/O stations    64 
  B : Number of remote device stations    42 
  C : Number of local stations, standby master stations, intelligent device stations    26 
 
CC-Link dedicated cable
CC-Link dedicated cable
Maximum 26
Terminating resistor 
(mandatory)
A1SJ61QBT11
AJ61QBT11
A1SJ61QBT11
AJ61QBT11
Master station
A1SJ61BT11
AJ61BT11
Local station
Local station
Maximum 64
Total 64
Remote I/O station
Remote device station
Intelligent device station
RS-232C 
Interface module
AJ65BT-R2N
Analog-digital
conversion module
AJ65BT-64AD
AJ65BTB    -       
AJ65BTC    -       
Remote I/O module
Maximum 42
Maximum 26