3 - 19 
3   SPECIFICATION 
MELSEC-QnA 
 
3.5 Buffer Memory 
The buffer memory is used to swap data between the master/local module and the 
programmable controller CPU. 
In the programmable controller CPU, the FROM/TO instructions are used to read/write 
data. 
The contents of the buffer memory return to the default values when the power is 
turned off and the programmable controller CPU is reset. 
 
3.5.1 Buffer memory list 
The buffer memory list is shown in Table 3.4. 
When using a master/local module as a standby master station, refer to the respective 
columns under "Availability" in the table as explained below. 
x
 When a standby master station is operating as a master station: "Master station" 
column 
x
 When a standby master station is operating as a standby master station: "Local 
station" column 
 
Table 3.4 Buffer memory list (1/2) 
 
Address 
Availability 
Hex. Dec. 
Item Details 
Read/write 
possibility 
Master station 
Local 
station 
Reference
0
H
 to 
5F
H
 
0 to 95 
Parameter information 
area 
Stores the information (parameters) 
to execute the data link. 
Read/write 
enabled 
 
(Not available when a 
standby master station is 
controlling the system) 
 
Section 
3.5.2 (1) 
60
H
 to 
7F
H
 
96 to 
127 
(Prohibited to use)  – 
– 
– 
– 
– 
80
H
 to 
CD
H
 
128 to 
205 
Parameter information 
area 
Stores the information (parameters) 
to execute the data link. 
Read/write 
enabled 
 
(Not available when a 
standby master station is 
controlling the system) 
 
Section 
15.2.1 
CE
H
 to 
DF
H
 
206 to 
223 
(Prohibited to use)  – 
– 
– 
– 
– 
When master station: Stores the 
input status from the remote/local 
station. 
 
– 
E0
H
 to 
15F
H
 
224 to 
351 
Remote input (RX) 
When local station: stores the input 
status from the master station. 
Read only 
– 
 
When master station: Stores the 
output status of the output to the 
remote/local station. 
Write only 
 
– 
160
H
 
to 
1DF
H
 
352 to 
479 
Remote output (RY) 
When local station: Stores the output 
status of the output to the master 
station. 
Read/write 
enabled 
– 
 
Section 
3.5.2 (2) 
When master station: Stores the 
transmission data to the remote/all 
local stations. 
Write only 
 
– 
1E0
H
 
to 
2DF
H
 
480 to 
735 
Remote register (RWw) 
(Master station:  
for sending 
Local station:  
for sending/receiving) 
When local station: Stores the 
transmission data to the 
master/other local stations. Also, 
stores the received data from the 
remote/other local stations. 
Read/write 
enabled 
– 
 
Section 
3.5.2 (3) 
: Usable  : Prohibited to use 