3   SPECIFICATION 
MELSEC-QnA 
 
(f)   Error invalid station specification 
This is set so that the remote/local station that can no longer perform data 
link due to power off, etc. will not be treated as a "data-link faulty station" on 
the master station and the local station. 
Be careful, however, for errors will not be detected. 
1
 When the same station number is specified as a reserved station, the 
reserved station specification has the priority. 
2
 Turn on the bit corresponding to the station number of the invalid station. 
However, for remote/local stations that occupy more than 2 stations, turn 
on the only bit for the station numbers set by the module's station 
number setting switch. 
1 to 64 in the table below indicate the station numbers. 
 
Address 
b15 b14 
b13 b12 
b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 
14
H
 
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 
15
H
 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 
16
H
 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 
17
H
 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 
 
<Setting example> 
When setting a local station with station number 4 and a remote station 
with station number 9 as invalid in the system configuration below: 
 
Set as invalid stations
Master
station
Remote station 
(occupies 2 stations)
Station No.1
Remote station 
(occupies 1 station)
Station No.3
Remote station 
(occupies 1 station)
Station No.8
Remote station 
(occupies 1 station)
Station No.9
 Local station
(occupies 4 
stations)
Station No.4
 
 
Address 
b15 b14 
b13 b12 
b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 
10
H
 
0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 
11
H
 
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
12
H
 
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
13
H
 
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0