6.6  Remote Operation
Remote operation allows to change the operating status of the CPU module externally (by GX Developer 
or external devices using the MC protocol, with link dedicated instructions of the CC-Link IE controller 
network module or MELSECNET/H module, or using remote contacts).
There are four types of remote operations:
6.6.1  Remote RUN/STOP
(1) Definition
This operation changes the operating status of the CPU module externally to RUN or STOP, keeping 
the RUN/STOP/RESET switch of the CPU module in the RUN position.
(2) Application
This operation is useful to run or stop the CPU module remotely when:
 • the CPU module is inaccessible, or
 • the CPU module is in a control panel.
(3) Program operation
The program operation will be as follows when the remote RUN/STOP operation is performed.
(a) Remote STOP
The CPU module executes a program until the END instruction and changes its operating status to 
STOP.
(b) Remote RUN
The CPU module changes its operating status to RUN and executes a program from the step 0. 
(The remote RUN operation must be performed to the CPU module whose operating status has 
been changed to STOP by the remote STOP operation.)
• Remote RUN/STOP
:
• Remote PAUSE
:
• Remote RESET
:
• Remote latch clear
: