6.
 R
e
mot
e
 O
p
erat
ion
6.
6.
 Rem
o
te
 PA
USE
6
 
-
 
21
6.6.2  Remote PAUSE
(1) Definition
This operation changes the operating status of the CPU module externally to PAUSE, keeping the 
RUN/STOP/RESET switch of the CPU module in the RUN position.
PAUSE status is a status where sequence program operations in the CPU module are stopped, 
holding the status (on or off) of all outputs (Y).
(2) Application
This operation is useful, especially during the process control, to hold the on status of outputs (Y) even 
after the operating status of the CPU module is switched from RUN to STOP.
(3) Executing method
There are two methods for performing the remote PAUSE operation.
 • Using a PAUSE contact
 • By GX Developer or an external device using the MC protocol
(a) Using a PAUSE contact
Set a PAUSE contact in the PLC system tab of the PLC parameter dialog box.
The settable device range is X0 to 1FFF
.
 •
The PAUSE contact (SM204) turns on during END processing of the scan where both the 
PAUSE contact and PAUSE enable coil (SM206) turn on.
The CPU module executes one more scan until the END instruction after the scan where the PAUSE 
contact turns on, and then changes its operating status to PAUSE. In the PAUSE status, the program 
operations are stopped.
 •
When the PAUSE contact or SM206 is turned off, the PAUSE status will be canceled and the 
CPU module will restart the sequence program operation from the step 0.
Setting of only a PAUSE contact is not allowed.
When setting a PAUSE contact, set a RUN contact as well.
Figure 6.17 Remote PAUSE using a PAUSE contact
OFF
ON
0
END
PAUSE status
0
END
0
0
END
END
SM206
OFF
ON
SM204
OFF
ON
RUN/PAUSE  
status
RUN
RUN
PAUSE
PAUSE 
contact
Turns on when the  
PAUSE conditions  
are established