Справочник Пользователя для Mitsubishi Electronics QnUCPU

Скачать
Страница из 630
6
 
-
 
34
6.11.1  
Monitor condition setting
This function is used to monitor data in the CPU module under the specified condition.
Note1
(1) Monitor condition setting for ladder monitor
Switch GX Developer into monitor mode.
Select [Online]   [Monitor]   [Monitor condition setup] to open the Monitor condition screen.
Set the condition as shown below to monitor data on the rising edge of Y70.
(a) When only a step number is specified
Monitor data is collected when the status immediately before execution of the specified step 
becomes the specified status.
The following status can be specified.
 • When the operation of the specified step changes from the non-execution status to the execution status: <-P->
 • When the operation of the specified step changes from the execution status to the non-execution status: <-F->
 • Always only when the operation of the specified step is in execution: <ON>
 • Always only when the operation of the specified step is in non-execution: <OFF>
 • Always regardless of the status of the operation of the specified step: <Always>
Note1
Figure 6.27 Monitor condition setting screen
Note6.1
The Q00UJCPU, Q00UCPU, and Q01UCPU do not support the monitor condition setting.
When setting monitor condition for the Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, or 
Q26UDHCPU, check the versions of the CPU module and GX Developer. (
Universal
Select to use a device as
a monitor condition.
Select to use a step
number as a monitor 
condition. 
Monitoring starts
when the condition is
established.
(An operation status
when the condition 
isestablished is 
displayed.)