6
 
-
 
162
6.32  Module error collection
Note1
(1) Definition
This function collects errors occurred in the connected intelligent function modules in the CPU module.
By storing the errors in a memory that can hold data in the event of a power failure, the errors can be held even 
after power-off or reset.
(2) Supported modules
The CPU module collects errors occurred in the connected intelligent function modules
*1
.
The CPU module does not collect the errors of intelligent function modules on other stations in the network.
*1: Indicates intelligent function modules that support this function. For supported module versions, refer to the manual for 
each module.
(3) Timing when module errors are collected
Module errors are not collected during execution of a program such as the COM instruction but collected in END 
processing.
Note1
Figure 6.125 Operation of module error collection
Note6.14
When using the module error collection, check the versions of the CPU module and GX Works2. (
GX Developer cannot display module errors. 
Universal
Error history display
19:29
19:33
19:34
19:35
Module A
CPU
Module B
Error A1
Error C1
Error B1
Error A2
Time Module in error Error code
Error history
(CPU module)
Module error log
Time Module in error Error code
19:29
19:34
19:36
ModuleA
ModuleB
ModuleA
Error A1
Error B1
Error A2
19:33 Error C1
CPU
19:29 Error A1 occurred!
19:36 Error A2 occurred!
19:34 Error B1 occurred!
Error history (CPU module) and error log (intelligent function module)
are displayed in one screen.
Errors that occurred in the entire system (base units) can be
monitored in reverse chronological order.
Error C1 occurred!
Module A
Module B
Programming tool
Module A
[Example of screen display]