Справочник Пользователя для Mitsubishi Electronics QnUCPU

Скачать
Страница из 630
CHAPTER9 DEVICES
9
2
3
4
5
6
7
8
9.
 I
n
te
rnal Us
er Dev
ice
9.
2.
5  
Ann
unciat
o
r (F
)
9
 
-
 
11
9.2.5  
Annunciator (F)
(1) Definition
The annunciator (F) is an internal relay which can be effectively used in fault detection programs for user-created 
system.
(2) Special relay and special register after annunciator ON
When the annunciator is turned on, the special relay (SM62) is set to on, and the numbers and 
quantity of the annunciator numbers are stored in the special register (SD62 to SD79).
The annunciator number stored in SD62 is also registered in the error history area.
(3) Applications of the annunciator
Using the annunciator in a fault detection program allows check for a system fault and identification of 
the fault (annunciator number) by monitoring the special register (SD62 to SD79) when the special 
relay (SM62) turns on.
  In this program, when annunciator (F5) is turned on, the corresponding annunciator number is output 
to the outside.
(4) Allowable number of 
normally open or closed contacts
There are no restrictions on the number of normally open or closed contacts used in a program, as 
long as the program capacity is not exceeded
.
• Special relay
: SM62
• • • Turns on even if only one of the annunciator number areas 
is turned on.
• Special register
: SD62
• • • Stores the number of the annunciator that was turned on 
first.
SD63
• • • Stores the quantity of the annunciator number areas that are 
on.
SD64 to 
SD79 
• • • Stores annunciator numbers in the order of turning on.
(The same annunciator number is  stored in SD62 and 
SD64.)
Figure 9.11 Detecting and saving the annunciator ON
Example
SD62
BCDP
SM62
SET F5
K4Y20
X0
X10
SM62
SD62
SD63
SD64
SD65
SD79
0
0
[Fault detection program]
Outputs No. of the  
annunciator that turned on.
Annunciator ON detection
OFF    ON
0    5
0    1
0    5