5.3 Serial Communication
5.3.12 PUTE instruction
5-103
G_PUTE
5
MODULE DEDICA
TED 
INSTRU
CTI
O
N
G_PUT
E
5.3.12  
PUTE instruction
G_PUTE
*1: Local devices and file registers per program cannot be used as setting data.
Function
This instruction registers a user frame.
Control Data
G(P)_PUTE
P: Executing condition
:
 indicates any of the following 
instructions.
G_PUTE
GP_PUTE
Input argument
EN:
Executing condition
:Bit
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in 
three digits)
:ANY16
s1:
Variable that stores control data
:Array of ANY16 [0..3]
s2:
Start number of the device that stores read registration data
:ANY16
Output argument
ENO:
Execution result
:Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data 
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
Device
Item
Setting data
Setting range
Setting side
[0]
Registration/deletion specification
Specify whether to register/delete the user frame of the 
number specified by 
[2].
1: Registered   3: Deleted
1, 3
User
[1]
Registration/deletion result
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
System
[2]
Frame No.
Specify the user frame number.
1000 to 1199
User
[3]
Number of registered bytes
1 to 80: Number of bytes of the user frame to be 
registered.
* Specify any number in the range from 1 to 80 as a 
dummy when '3: Deleted' is selected.
1 to 80
User
Serial
Structured ladder/FBD
ST
G_PUTE
EN
ENO
Un*
s1
s2
d
G_PUTE
(EN, Un*, s1, s2, d);
ENO:=
s1
s2
d
s1
s1
s1
s1
s1