5-152
5.4 Network Dedicated Instruction
5.4.9 SREAD instruction
J_SREAD, G_SREAD
5.4.9  
SREAD instruction
J_SREAD, G_SREAD
*1: Local devices and file registers per program cannot be used as setting data.
J(P)_SREAD
G(P)_SREAD
P: Executing condition
:
 indicates any of the following 
instructions.
J_SREAD
JP_SREAD
G_SREAD
GP_SREAD
Input argument
EN:
Executing condition
:Bit
Jn*:
Network number of the host station (1 to 239, 254)
254: Network specified in 
"
Valid module during other station 
access
"
:ANY16
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in 
three digits)
:ANY16
s1:
Variable that stores control data
:Array of ANY16 [0..17]
s2:
Start number of the target station's device from which data are 
read
:ANY
Output argument
ENO:
Execution result
:Bit
d1:
Start number of the host station's device that stores read data :ANY16
d2:
Variable that turns ON upon completion of the instruction
d2[1] also turns ON at the time of error completion.
:Array of bit [0..1]
d3:
Variable that turns ON upon completion of the instruction
(read notification device)
:Bit
Setting
data 
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
CC IE F
CC IE C
NET/H
Ether
Structured ladder/FBD
EN
ENO
Jn*
d1
d2
s1
s2
J_SREAD
EN
ENO
Un*
d1
d2
d3
d3
s1
s2
G_SREAD
ST
J_SREAD
(EN, Jn*, s1, s2, d1, d2, d3);
ENO:=
G_SREAD
(EN, Un*, s1, s2, d1, d2, d3);
ENO:=
s1
s2
d1
d2
d3