5-192
5.4 Network Dedicated Instruction
5.4.16 ZNRD instruction
J_ZNRD
5.4.16  
ZNRD instruction
J_ZNRD
*1: Local devices and file registers per program cannot be used as setting data.
*2: In addition to the setting data, the ZNRD instruction is executed using the following fixed values. 
Channel used by host station: Channel 1
Arrival monitoring time (monitoring time until instruction completion): 10 seconds
Number of resends for arrival monitoring timeout: 5 times
J(P)_ZNRD
P: Executing condition
:
 indicates any of the following 
instructions.
J_ZNRD
JP_ZNRD
Input argument
EN:
Executing condition
:Bit
Jn*:
Network number of the host station (1 to 239)
:ANY16
n1:
Target station number (1 to 64)
:ANY16
s
Target station's start device number where data to be read are 
stored
:ANY16
n2:
Read data length
When the target station is Q/QnA/AnUCPU: 1 to 230 words
When the target station is anything other than Q/QnA/
AnUCPU: 1 to 32 words
:ANY16
Output argument
ENO:
Execution result
:Bit
d1:
The host station's start device number where readout data will 
be stored
(A contiguous area for the read data length is required.)
:ANY16
d2:
The host station's device that is turned on for one scan upon
completion of the instruction
d2[1] also turns ON if the instruction execution has failed.
:Array of bit [0..1]
Setting
data 
*1,*2
Internal device
R, ZR
J
\
U
\G
Zn
Constant
K, H
Others
Bit
Word
Bit
Word
n1
n2
CC IE C NET/H
Ether
Structured ladder/FBD
J_ZNRD
EN
ENO
Jn*
d1
d2
s
n2
n1
ST
J_ZNRD
(EN, Jn*, n1, s, n2, d1, d2);
ENO:=
s
d1
d2